Altronix AL602ULADA Instalační příručka Strana 2

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 16
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 1
- 2 - AL602ULADA
Agency Listings:
• ULListedControlUnitsandAccessoriesfor
FireSystems(UL864).
• MEA-NYCDepartmentofBuildingsApproved.
• CSFM-CaliforniaStateFireMarshalApproved.
• FM-FactoryMutualApproved.
• NFPA72Compliant.
Input:
• Powerinput120VAC60Hz,4amp.
• Two(2)ClassA,StyleZortwo(2)ClassB,
StyleW,X,YFACPinputs.
• Two(2)NCdrycontacttriggerinputs.
Output:
• 24VDC@6.5ampmaxtotalalarmcurrent.
• 2.5ampmaxcurrentperoutput.
• Separate1.0ampauxiliaryoutput.
• Two(2)outputsmaybeparalleledformorepoweronan
indicatingcircuit(see 02 Application Guide).
• Programmablesupervisedindicatingcircuitoutputs:
Four(4)ClassB,StyleW,X,YorTwo(2)ClassA,
StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB,
StyleW,X,Y(see 02 Application Guide).
•Thermalandshortcircuitprotectionwithautoreset.
Battery Backup:
• Chargingvoltageis26.2-26.4VDC.
•Built-inchargerforsealedleadacidorgeltypebatteries.
•Automaticswitchovertostand-bybatterywhenACFails.
• Zerovoltagedropwhenswitchingovertobatterybackup.
Supervision:
•ACfailsupervision(form“C”contact,1amp/28VDC).
Factorysetfor30secondswithoptional2.5to3hour
delaysetting(fieldselectable).
Supervision (cont’d):
• InstantlocalACtroublereportingrelay
(form“C”contact,1amp/28VDC).
•Batterypresenceandlowbatterysupervision
(form“C”contact,1amp/28VDC).
Visual Indicators:
•InputandoutputstatusLEDindicators.
Special Features:
• 2-wirehorn/strobeSyncmodeallowsaudible
notificationappliances(horns)tobesilenced
whilevisualnotificationappliances(strobes)
continuetooperate.
• SyncprotocolsincludePotter/Amseco,Faraday,
Gentex
®
,
SystemSensor
®
,andCooperWheelock
®
.
• TemporalCode3,SteadyMode,InputtoOutput
FollowerMode(maintainssynchronizationof
notificationappliancescircuit).
• Compatiblewith12VDCor24VDCfirepanels.
•Outputloopsupervisionsteeredtoinput1orinput2.
• Signalcircuittroublememory(helpsidentify
intermittentloopproblems).
• Commontroubleinputandoutputforexternaltrouble
signalstie-in.
• Groundfaultdetection.
•Unitincludespowersupply,redenclosure,camlock,
andbatteryleads.
Enclosure Dimensions (approx. H x W x D):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm).
Overview:
TheAltronixAL602ULADAisanextremelycosteffective6.5ampremotepowersupply/batterycharger.Itmaybe
connectedtoany24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit
(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupport
systemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,X,YorClass
A,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavailable.
The6.5ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputis
ratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.
AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Anindividualoutputof4
ampisachievedbyparalleling2outputs.Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/
orClassB,StyleW,X,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedvia
thesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareused
toindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devices
toreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionand
powerdeliverytoanycombinationofthefour(4)outputs.
Specifications:
AL602ULADA - NAC Power Extender
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
Zobrazit stránku 1
1 2 3 4 5 6 7 ... 15 16

Komentáře k této Příručce

Žádné komentáře